The recovery equipment shall be in good working order with a set
of instructions concerning the equipment that is at hand and shall
be suitable for the recovery of the flammable refrigerant. If in
doubt, the manufacturer should be consulted. In addition, a set of
calibrated weighing scales shall be available and in good working
order. Hoses shall be complete with leak-free disconnect cou-
plings and in good condition.
The recovered refrigerant shall be processed according to local
legislation in the correct recovery cylinder, and the relevant waste
transfer note arranged. Do not mix refrigerants in recovery units
and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that
they have been evacuated to an acceptable level to make certain
that flammable refrigerant does not remain within the lubricant.
The compressor body shall not be heated by an open flame or oth-
er ignition sources to accelerate this process. When oil is drained
from a system, it shall be carried out safely.
Evaporator Coil Removal
VERTICAL CONFIGURATION UNITS
For vertical configuration units, the evaporator coil can be re-
moved from the front side of the unit (refer to Fig. 50 ). Follow
these steps:
1. Shut off the main power supply to the unit and apply
lock-out/tag-out procedures.
2. Remove the upper front panel.
3. Open the front lower access panel with the control box.
4. Disconnect electrical power and lift off the access panel to
remove it.
5. Remove the remaining front brace located between the upper
and lower panels.
6. Slide out and remove the blower assembly.
7. Disconnect the refrigerant pipes connected to the evaporator
coil (requires cutting the pipes).
8. Remove the screws from the full side panel.
9. Pivot out and remove the evaporator coil.
NOTE: Evaporator removal/replacement requires cutting/brazing
pipes. Follow the Refrigerant Removal, Evacuation, and Charging
procedures in the Service section on page 70.
Ensure all steps are followed for safe and efficient removal of the
evaporator coil.