Carrier NSA-DIFFER-LO handleiding
Handleiding
Je bekijkt pagina 1 van 9

Differential Low Pressure
Installation and Operation
#NSA-HH/DLP-001-W-U-D-A-3-C, NSA-HH/DLP-001-W-U-N-A-0-C, NSA-HH/DLP-010-W-U-D-A-3-C
NSA-HH/DLP-010-W-U-N-A-0-C, NSA-HH/DLP-040-W-U-D-A-3-C, NSA-HH/DLP-040-W-U-N-A-0-C – 11/14/2019
Specifications subject to change without notice.
Catalog No. 11-808-753-01 Page 1 of 9
Overview
The DLP Series is based on a piezoresistive, silicon sensing element which senses Differential
Pressure and provides an analog output. The hinged cover on the DLP can be easily opened using
the integrated locking tab on the side of the enclosure. This allows for easy access to the zero
function and field selectable ranges and outputs. The DLP Series also includes an optional, five digit
LCD for installation and monitoring support. Field selectable analog outputs include 0-5 and 0-10
VDC, or 4-20 mA which correlate to a uni or bi-directional pressure range from 0-0.1” up to 0-40” of
water column, depending on your model selection. Each unit has up to 8 field selectable, uni or bi-
directional ranges. Options include a Pitot Tube or Din Rail Clip.
Applications: Building and Duct Static Pressure, Filter Monitoring, Air Flow Measurement, and
Process Control
Part Numbers
NSA-HH/DLP-001-W-U-D-A-3-C NSA-HH/DLP-001-W-U-N-A-0-C NSA-HH/DLP-010-W-U-D-A-3-C
NSA-HH/DLP-010-W-U-N-A-0-C NSA-HH/DLP-040-W-U-D-A-3-C NSA-HH/DLP-040-W-U-N-A-0-C
Specifications
Supply Voltage:
4-20 mA Output: 16-36 VDC (250 Ohm Load max.) / 22-36 VDC (500 Ohm Load max)
0-5 VDC / 0-10 VDC Output: 16-36 VDC / 24 VAC (+/- 10%)
Supply Current:
4-20 mA Output: 24 mA min (0.83 VA) | 0-5 VDC / 0-10 VDC Output: 6 mA max (0.18 VA)
Output Signals:
Current Output: 4-20 mA, 2-Wire Loop Powered (Default); Current limited to 21.5 mA max
Voltage Signals: 0-5 VDC / 0-10 VDC Field Selectable, 3-Wire; Output limited @ 5.25 & 10.5 VDC
Response Time (0-100%
FSO):
4 seconds
Output Update Rate:
0.5 second intervals
Pressure Ranges:
(Defaults in bold)
NSA-HH/DLP-001: 0-0.1", 0.2", 0.5", 1" ±0.1", ±0.2", ±0.5", ±1"
NSA-HH/DLP-010: 0-1", 2", 5", 10" ±1", ±2", ±5", ±10"
NSA-HH/DLP-040: 0-10", 20", 30", 40" ±10", ±20", ±30", ±40"
Maximum Pressure
NSA-HH/DLP-001: 1WC | NSA-HH/DLP-010: 10 WC | NSA-HH/DLP-040: 40 WC
Accuracy
1
:
+/- 0.50% FSO
Zero Function:
Pushbutton Zero Function
Thermal Effects
2
:
+/- 0.067% FSO / °F (0.12% FSO / °C)
Proof Pressure | Burst
Pressure:
NSA-HH/DLP-001: Proof: 270 inWC (67.2 kPa) | Burst: 415 inWC (103.3 kPa) for 1 inWC (249.8 Pa)
NSA-HH/DLP-010: Proof: 350 inWC (87.12 kPa) | Burst: 550 inWC (136.9 kPa) for 10 inWC (2490.8
Pa)
NSA-HH/DLP-040: Proof: 562 inWC (140 kPa) | Burst: 1004.7 inWC (250 kPa) for 40 inWC (9963.6
Pa)
Operating Temp Range:
-4 to 185°F (-20 to 85°C)
Compensated Temp
Range:
32 to 122°F (0 to 50°C)
Storage Temp Range:
-22 to 185°F (-30 to 85°C)
Operating Humidity
Range:
10 to 95% RH, non-condensing
Media Types:
Intended for use with non-corrosive, non-ionic gases, such as air and other dry gases
Enclosure Material |
Flammability Rating:
Flame Retardant Polycarbonate; UL94-5VA
Wiring Connections:
Finger Pushbutton (Spring) Terminal Blocks; accepts 16-24 AWG wires
Conduit Knockouts:
Watertight Cordgrip Installed (1/2" NPT Conduit fittings accepted when Cordgrip removed)
Pressure Fitting Material:
Nickel Plated Brass or Stainless Steel
Bekijk gratis de handleiding van Carrier NSA-DIFFER-LO, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Carrier |
Model | NSA-DIFFER-LO |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 1501 MB |