Introduction FOUNDATION Fieldbus Communication
Table 6 - Range Limits for DP Transmitters
Code
Range Limits
B
-50 and +50 kPa (-200 and +200 inH
2
O)
C
-250 and +250 kPa (-1000 and +1000 inH
2
O)
D
-0.10 and +2.07 MPa (-14.7 and +300 psi)
E
0 and 21 MPa (0 and 3000 psi)
Maximum Static, Overrange, and Proof Pressure Ratings
DANGER
HAZARD OF EXPLOSION
Exceeding the proof pressure can cause the sensor to rupture forcefully. Avoid
exposing the transmitter to the proof pressure limit.
Failure to follow these instructions will result in death or serious injury.
NOTICE
POTENTIAL EQUIPMENT DAMAGE
Exceeding the overrange pressure limit for the transmitter can cause damage to the
transmitter, degrading its performance. The transmitter could become nonfunctional
after exceeding the overrange pressure. Avoid exposure to the overrange pressure
limit.
Failure to follow these instructions can result in equipment damage.
Ratings for Direct Connect AP and GP Transmitters
Table 7 - Maximum Overrange and Proof Pressure for Direct Connect
Transmitters
Span Limit
Code
Maximum Overrange Pressure Maximum Proof Pressure
16
D 2.1 MPa (300 psi) 5.51 MPa (800 psi)
E 20.7 MPa (3,000 psi) 55.1 MPa (8,000 psi)
F
17
59.1 MPag (8,580 psig) 165 MPa (24,000 psig)
Ratings for DP Transmitters and Biplanar AP and GP Transmitters
For DP transmitters and for AP and GP transmitters with biplanar structures, pressure
ratings may be affected by bolting options and other model code selections.
MI 020-612 15
16. Meets ANSI/ISA Standard S82.03-1988.
17. Available for gauge pressure transmitters only.