Table 11 — Second Data Plate for Units with 20 kW Electric Heater (EH) Option and
Constant Airflow ECM Motor
a,b
50WD UNIT
SIZE
VOLTAGE/
Hz/ PHASE
VOLTAGE
MIN/MAX
BLOWER MOTOR
20 kW ELECTRIC HEATER
Heater Element 2nd Data Plate Values
Watts Amps MCA MOP
FLA Hp 208-v 240-v 208-v 240-v 208-v 240-v 208-v 240-v
048 208-230/1/60 197/253 8.4 0.75 14.4 k 19.2 k 69.3 80.0 97.2 110.5 90 110
060 208-230/1/60 197/253 9.1 1.00 14.4 k 19.2 k 69.3 80.0 98.0 111.4 90 110
070 208-230/1/60 197/253 9.1 1.00 14.4 k 19.2 k 69.3 80.0 98.0 111.4 90 110
NOTE(S):
a. Units with Factory Installed Electric Heat option will have two separate data plates for each electrical circuit.
b. Electric heat is not available for horizontal-straight through airflow configuration.
LEGEND
EH — Electric Heat
FLA — Full Load Amps
Hp — Horsepower
LRA — Locked Rotor Amp
RLA — Rated Load Amps
MCA — Minimum Circuit Amps
MOP — Maximum Overcurrent Protection