Introduction FOUNDATION Fieldbus Communication
Standard Specifications
Operative Limits
Influence Operative Limits
1
Sensor Body Temperature
2
PVDF inserts -7 and +82°C (+20 and 180°F)
Silicone fill fluid -46 and +121°C (-50 and +250°F)
3 4
Fluorinert fill fluid -29 and +121°C (-20 and +250°F)
5
NEOBEE
®
fill fluid -18 and +121°C (0 and 250°F)
Electronics Temperature
Without LCD -40 and +85°C (-40 and +185°F)
6 7
With LCD -40 and +85°C (-40 and +185°F)
6 7 8
Relative Humidity 0 and 100%
9
Supply Voltage 9 V dc and 32 V dc
Mounting Position No limit
Vibration
Aluminum Housing Per IEC 60770 for “field with high vibration level or pipeline with high vibration
level”: 0.42 mm peak-to-peak displacement from 10 to 60 Hz, 3 “g” constant
acceleration input over a frequency range of 60 to 1000 Hz
Stainless Steel Housing Per IEC 60770 for “field with general application or pipeline with low vibration
level”: 0.3 mm peak-to-peak displacement from 10 to 60 Hz, 2 “g” constant
acceleration input over a frequency range of 60 to 1000 Hz
Span and Range Limits
Limits for Direct Connect Transmitters
Table 1 - Span Limits for Direct Connect Transmitters
Code
Span Limits
10
D
3.4 and 1380 kPa (0.5 and 200 psi)
E
0.034 and 13.8 MPa (5 and 2000 psi)
F
0.52 and 41.4 MPa (75 and 6000 psi)
11
MI 020-612 13
1. Normal Operating Conditions and Operative Limits are defined per ANSI/ISA 51.1-1979 (R1993)
2. Refer to MI 020-369 for temperature limits with pressure seals.
3. Selection of Option -J extends the low temperature operative limit of transmitters with silicone filled sensors down to -50°C (-58°F).
Performance is not assured below -29°C. Sensor damage may occur if process is frozen. Contact Global Customer Support for availability of
this option.
4. -46 and +50°C (-50 and +122°F) for biplanar AP transmitters.
5. -18°C (0°F) for J range (IGP05S transmitters only).
6. -40 and +75°C (-40 and +167°F) for transmitters with ATEX flameproof classification.
7. -40 and +50°C (-40 and +122°F) for biplanar AP transmitters.
8. Display updates are slowed and readability is decreased at temperatures less than -20°C (-4°F).
9. Relative humidity refers to transmitters with housing covers installed and conduit entrances sealed. To maintain IEC IP66/IP67 and NEMA
Type 4X protection, plug the unused conduit opening with the metal plug provided. Use a suitable thread sealant on both conduit connections.
In addition, the threaded housing covers must be installed. Turn covers to seat the o-ring into the housing, then continue to hand-tighten until
the cover contacts the housing metal-to-metal.
10. Values listed are in absolute or gauge pressure units, as applicable.
11. Available for gauge pressure transmitters only.