Transfer Voltage and Sensitivity Settings
Voltage regulation
The Back-UPS will switch to battery power if the AC input voltage level
becomes too low or too high, or if the AC power is experiencing voltage
fluctuations.
No-load shutdown
The UPS will shut down to conserve energy if while operating on battery
power the UPS detects that connected equipment is using less than 15 W of
energy for more than 15 minutes.
Disable this feature if low power consuming equipment like ADSL-modem or
wi-fi router is connected to the Back-UPS.
No-load shutdown can be enabled or disabled through Program mode
described below.
Voltage sensitivity adjustment
If the Back-UPS switches to battery power too frequently or too infrequently,
adjust the transfer voltage and sensitivity settings:
1.
Verify that the Back-UPS battery is connected. Connect the Back-UPS to a wall
outlet. The Back-UPS should be turned off.
2. Press and hold the POWER ON/OFF button until the LED continuously flashes
green. Release the button. The Back-UPS is now in Program mode.
3. The LED will flash once, twice, or three times per second, and emit audible
beeps to indicate the current sensitivity level. The Back-UPS will beep to
indicate that No-load Shutdown is enabled. Refer to the table for an explanation
of the transfer voltage sensitivity levels.
4. Press the POWER ON/OFF button within two seconds to change the setting.
Continue pressing the button until the desired setting is reached. If the button is
not pressed within five seconds, the Back-UPS will exit the Program Mode.
5. To select LOW sensitivity, press the POWER ON/OFF button until the LED
flashes green once per second.
6. To select MEDIUM sensitivity, press the POWER ON/OFF button until the LED
flashes green two times per second.
7. To select HIGH sensitivity, press the POWER ON/OFF button until the LED
flashes green three times per second.
8. To exit Program mode wait for five seconds, the LED will extinguish. Program
mode is no longer active.