Checking the installation
Position of the commutation reactor
If the frequency inverter is connected to an external commutation reactor, then the braking unit must be connected to the line supply
(diagram below). If the braking unit is connected downstream of the commutation reactor, then the inductance of the reactor prevents the
braking unit from synchronizing on the line supply and generates overvoltages, which can result in damage to the components of the braking
unit.
Same warning about the presence, also not permitted, of other commutation reactors upstream of the braking unit.
CAUTION
RISKS OF INTERFERENCE
Overvoltages can cause serious damage to the frequency inverter and/or the braking
unit and the other loads.
Failure to follow this precaution can result in equipment damage.
M
60kW
ATV71
VW3A7...
Prohibited