Checking the installation
Operation on a transformer
If only some loads are operating on one section of the line supply, then the transformer that is connected must be capable of transporting
the unused generated power from this section to the next voltage level without exceeding the voltage edge permitted in the line supply
section. The nominal power of the transformer must therefore be one and a half times greater than the power generated outside the section,
so that the harmonic and reactive components of the current can be transmitted. In the line supply section shown in the diagram below,
these conditions are verified even if the other loads are disconnected.
If the power that is generated is in the region of the nominal power of the transformer, then the transformer short circuit voltage must be
fairly low (6% maximum) to limit the voltage increase in this section.
The operation of the braking unit used with a sized transformer (for example in the case of a slip ring induction motor) is only permitted if
the ratio of the power generated to the nominal power is considerably less than 1.
M
M
R
Tr
10kV
0.4kV
100kVA
60kW
20kW
20kW
ATV71
VW3A7...