Operating Principle
Compensation for loss of head (up to the version V1.1IE02)
An additional step [Pr adj coeff] (O14) is automatically added to the reference value each time an auxiliary pump is started. These reference
steps compensate for a loss of pressure (loss of head) in the pipework due to an increase in flow rate.
• Compensation for loss of head is active when the [Pr adj coeff] (O14) parameter is other than 0.
• The new PID regulator reference is generated using "PID preset reference 2" [Preset ref. PID 2] (rP2).
The [Preset ref. PID 2] (rP2) parameter is controlled by the pump switching card. It is therefore not possible to use the "PID
preset references" function with the "Compensation for loss of head" function.
Example of using the PID regulator with an internal reference:
• [Internal PID ref.] (rPI) = 400 (internal reference)
• [Min PID feedback] (PIF1) = 200
• [Max PID feedback] (PIF2) = 1000
• [Pr adj coeff] (O14) = 50
Each time an auxiliary pump is started the reference becomes:
- variable pump + 1 auxiliary pump: new reference = 450
- variable pump + 2 auxiliary pumps: new reference = 500
- variable pump + 3 auxiliary pumps: new reference = 550
PID regulator reference
O14
O14
O14
Time
Run
Run
Run
Stop
Stop
Stop
Auxiliary pump 1
Auxiliary pump 2
Auxiliary pump 3
PID reference
Compensated
PID references