Operating Principle
Selecting the operating mode
The pump switching card provides 9 possible operating modes. These modes combine: the choice of variable pump, the choice of auxiliary
pump and limitation of relative operating time.
The mode is selected using the [Op. mode] (O01) parameter, ([1.14 Multi pump] (En -) menu).
Controlling an auxiliary pump
The PI regulator output (frequency reference of the variable pump) is used to control starting or stopping of an auxiliary pump with
hysteresis, as shown in the figure below:
When the frequency exceeds the starting threshold ([FrqAuxPumpOn] (O12) parameter), a time delay ([Pump Delay On] (O03)
parameter) is started to avoid the effects of transient flow fluctuations. If after this time delay, the frequency remains higher than the starting
threshold, another pump is started. When the start command is sent, a time delay ([Acc Aux Pump] (O06) parameter) is started to allow
the pump to reach its nominal speed before starting another pump (avoids oscillation).
When the frequency is below the stopping threshold ([FrqAuxPumpOff] (O13) parameter), a time delay is started ([Pump Delay Off] (O04)
parameter) to avoid the effects of transient flow fluctuations. If after this time delay, the frequency remains below the stopping threshold, a
pump is stopped. When the stop command is sent, a time delay ([Dec Aux Pump] (O07) parameter) is started to allow the pump to reach
an effective stop before stopping another pump (avoids oscillation).
"Sleep" function/"Wake up" function
This function is used to stop the variable pump when the flow rate is zero (all the auxiliary pumps are off).
In this case, if the frequency of the variable pump is below the "sleep" threshold ([Sleep thresh] (O15) parameter), a time delay
([SleepFunctDel] (O05) parameter) is started. If, after this time delay [SleepFunctDel] (O05), the frequency remains below the [Sleep
thresh] (O15) threshold, the variable pump then stops. The installation is in "sleep" state.
To switch to "wake up" state, the pressure feedback must drop to below the "wake up" threshold ([WUp thresh] (O16) parameter). The
variable pump is then started.
Startup
of an auxiliary pump
Frequency
corresponding to the flow
rate of an auxiliary pump
Flow rate of the installation
Frequency of the
variable pump
HSP
Starting
frequency
Stopping
frequency
Stop of an
auxiliary pump
t
t
LSP
Sleep threshold operating time
PI feedback
Motor
frequency
[WUp thresh] (O16)
[Sleep thresh] (O15)
[SleepFunctDel] (O05)