9. Configuration
Switching of control and setpoint from BACnet to the terminals without application function
Input LI5 is used to switch the control and the setpoint between BACnet and the terminals. When switched to the terminals, the application
functions (summing…) are not active.
Configure the following parameters:
Configuration via the graphic display terminal or the integrated display terminal:
Parameter Value Comment
Profile Non separate profile The command and the setpoint come from the same channel.
Setpoint 1 configuration Network card Setpoint 1 and command 1 comes from BACnet.
Setpoint 2 configuration Analog input 1 on the terminals Setpoint 2 and command 2 comes from input AI1 on the terminals.
Setpoint switching Input LI5 Input LI5 switches the setpoint (1
↔ 2) and the command.
Menu Parameter Value
[1.6 - COMMAND] (CtL-) [Profile] (CHCF) [Not separ.] (SIM):default value
[Ref.1 chan] (Fr1) [Com. card] (nEt)
[Ref.2 chan] (Fr2) [AI1 ref.] (AI1)
[Ref.2 switching] (rFC) [LI5] (LI5)
BACnet