9. Configuration
9. 2. Control
Numerous configurations are possible. For more information, refer to the Programming Manual and the Parameters Manual.
The following configurations are just some of the possibilities available.
b Allowed configurations
If the drive is only monitored by BACnet:
There is no configuration constraint.
If the drive is controlled by BACnet:
The parameter [Profile] (CHCF) must be configured to [Not separ.] (SIM) or [Separate] (SEP). [Not separ.] (SIM) is the default value.
It is not allowed to configure the parameter [Profile] (CHCF) to the value [8 serie] (SE8) or [I/O profile] (IO).
If a forbidden configuration is done, the drive will trip on [External fault com.] (EPF2).
b Control via BACnet
The command and the setpoint come from BACnet.
Configure the following parameters:
Configuration via the graphic display terminal or the integrated display terminal:
Parameter Value Comment
Profile Non separate CiA402 profile The run command are in CiA402 profile the command
and the setpoint come from the same channel.
Setpoint 1 and command configuration Network card The setpoint and command come from BACnet.
Menu Parameter Value
[1.6 - COMMAND] (CtL-) [Profile] (CHCF) [Not separ.] (SIM):default value
[Ref.1 chan] (Fr1) [Com. card] (nEt)