When an alarm goes off, it is possible to acknowledge it pressing OK key on the transmitter: the audible alarm, if it is
activated, turns off and the displayed value blinks during the acknowledgement duration (from 0 to 60 minutes). At
the end of the acknowledgement duration, if the transmitter is still in alarm state, the audible alarm is reactivated.
3.5.2 Set the alarm in rising or falling edge
The alarm mode “Rising edge” or “Falling edge” is selected.
➢ Go to the “Conguration” line then press OK.
➢ Press OK on the “Channel” line and select the channel where the alarm will be active.
➢ Press OK to validate.
➢ Go to the “Threshold” line then press OK.
➢ Use Up/Down/Left/Right arrows to enter a threshold then press OK.
➢ Go to the “Hysteresis” line then press OK.
➢ Use Up/Down/Left/Right arrows to enter the hysteresis value then press OK.
➢ Go to the line “Threshold delay” then press OK.
➢ Use Up/Down/Left/Right arrows to enter the value of threshold delay in second then press OK (this value is
between 0 and 600 s).
➢ Go to the line “Hysteresis threshold” then press OK.
➢ Use Up/Down/Left/Right arrows to enter the value of the hysteresis delay in second then press OK (this value is
between 0 and 600 s).
➢ Go to the “Sound alarm” line then press OK.
➢ Select “YES” to activate the audible alarm or “NO” not to activate it then press OK.
➢ Go to the line “Acknowledgement duration” then press OK.
➢ Use Up/Down/Left/Right arrows to enter the value of the alarm acknowledgement in minute then press OK (this
value is between 0 and 60 minutes).
3.5.3 Configure the alarm in monitoring mode
The alarm mode “Monitoring” is selected.
➢ Go to the “Conguration” line then press OK.
➢ Press OK on the “Channel” line and select the channel where the alarm will be active.
➢ Go to the “Threshold 1” line then press OK.
➢ Use Up/Down/Left/Right arrows to enter the threshold 1 then press OK.
➢ Go to the “Threshold 2” line then press OK.
➢ Use Up/Down/Left/Right arrows to enter the threshold 2 then press OK.
➢ Go to the “Delay 1” line then press OK.
➢ Use Up/Down/Left/Right arrows to enter the value of the time-delay of the alarm activation in second then press
OK (this value is between 0 and 600 s).
➢ Go to the “Delay 2” line then press OK.
➢ Use Up/Down/Left/Right arrows to enter the value of the time-delay to return to a normal state in second then
press OK (this value is between 0 and 600 s).
Congure the transmitter
17
Monitoring
The alarm goes off when the measurement is outside the low and
high thresholds.
*Only available with the pressure board