5.2 Test Operation of Control Unit
5.2.1 Prepare the Control Unit
1. Shut power off to the control box.
WARNING
Turnoffthepowertothecontrolboxbeforestarting
thisprocedure.Failuretocomplymaycauseashock
hazard,resultinginseverepersonalinjuryordeath.
CAUTION
Besuretoseparatewiressothattheyarenot
touchingeachotherordamagemayresulttothe
controlbox.
2. Disconnect the sensor from the sensor wires. Refer
to Figure 7, Control Box Wiring, on page 10, and
Table 1, Sensor Wire Connections, on page 11.
a. Disconnect the black wire for the Sensor
Common probe from the yellow wire in the
control box.
b. Disconnect the red wire for the Fill Sensor
probe from the yellow wire with the blue
stripe in the control box.
c. Disconnect the white wire for the High Water
Sensor probe from the yellow wire with the
red stripe in the control box.
3. Disconnect the valve and the relay from the
control box. Refer to Figure 7, Control Box
Wiring, on page 10, and Table 5, shown below.
a. Disconnect the valve from the blue wires in
the control box.
b. Disconnect the relay from the red and gray
wires in the control box.
Valve or Relay Control Box Wires
Valve Wires Blue
Relay Wires Red and Gray
Section 5. Troubleshooting
Tools required: Multimeter that can read AC and DC
voltage and No. 6 Phillips screwdriver.
5.1 Observations at Job Site
Make these initial observations when at the jobsite.
1. Proper wire usage between the controller and the
valve. (Direct-burial style polypropelene-jacketed
solid-core wire (at least 18-gauge wire): the same
wire as the sensor wire.)
2. Proper wire nuts at the valve connection. (Grease-
lled wire nuts or gel caps. Conventional wire
nuts lled with silicone will not work since some
silicones have acids that degrade copper wires.)
3. Sensor wire is continuous and not spliced. (No
splices between the tips and the controller.)
4. Proper use of appropriate sensor and location: slip
style for static pipes.
5. Proper power input voltage to the box and proper
wiring for the voltage (110 or 220VAC).
6. Remove top face plate to verify that control lights
on PCB line up with plastic lenses on the plate.
NOTE Beforemakingchangestoconnectionsor
settings,resetthecontrollerbypoweringofffor
10secondsandthenpoweringbackon.
Table 5. Valve and Relay Connections
Page 16
ENGLISH
Jandy Pro Series Levolor
®
II Electronic Water Leveler
Models K-2000
|
Installation and Operation Manual