2
GENERAL
These installation instructions cover the 50FC units with cooling
only. Units are pre-wired and pre-charged with environmentally
balanced Puron
®
(R-410A) refrigerant at the factory. See Fig. 1 for
model number nomenclature. See Fig. 2-16 for unit dimensions.
See Fig. 5, 10, and 15 for service clearances.
Rated Indoor Airflow (cfm)
Table 1 lists the rated indoor airflow used for the AHRI efficiency
rating for the units covered in this document.
NOTE: Unit is not designed to have overhead obstruction. Contact
Application Engineering for guidance on any application planning
overhead obstruction or for vertical clearances.
DANGER
ELECTRICAL SHOCK HAZARD
Failure to follow this warning will result in personal injury or
death.
Before performing service or maintenance operations on unit,
turn off main power switch to unit and install lock(s) and
lockout tag(s). Ensure electrical service to rooftop unit agrees
with voltage and amperage listed on the unit rating plate. Unit
may have more than one power switch.
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury,
death and/or equipment damage.
R-410A refrigerant systems operate at higher pressures than
standard R-22 systems. Do not use R-22 service equipment or
components on R-410A refrigerant equipment.
WARNING
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause personal injury or
death.
Relieve pressure and recover all refrigerant before system
repair or final unit disposal.
Wear safety glasses and gloves when handling refrigerants.
Keep torches and other ignition sources away from
refrigerants and oils.
CAUTION
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing, safety glasses and gloves
when handling parts and servicing air conditioning equipment.
Table 1 — Rated Indoor Airflow (cfm)
MODEL NUMBERS FULL LOAD AIRFLOW (cfm)
50FC-*20 6,125
50FC-*24 7,000
50FC-*28 8,750
50FC-*30 10,000