Differential Low Pressure
Installation and Operation
#NSA-HH/DLP-001-W-U-D-A-3-C, NSA-HH/DLP-001-W-U-N-A-0-C, NSA-HH/DLP-010-W-U-D-A-3-C
NSA-HH/DLP-010-W-U-N-A-0-C, NSA-HH/DLP-040-W-U-D-A-3-C, NSA-HH/DLP-040-W-U-N-A-0-C 11/14/2019
Specifications subject to change without notice.
Catalog No. 11-808-753-01 Page 7 of 9
Zero Function
The DLP unit should be “ZEROED” before pressure is applied to the unit. The zero button is used to cancel out any offsets
caused by installation and sensor drift. The Zero adjustment must be performed with NO pressure applied to either side of
the sensor.
Remove the tubing connected to the H(High) and/or L(Low) pressure fittings. Push “ZERO” button for more than three
seconds before installation or whenever necessary
For units with LCD display, “AUTOZERO” icon will be on when the unit enters zero mode. If zeroing process is successful,
the “AUTOZERO” icon will flash twice.
Figure 8
Pressure Range Selection
If a custom calibrated pressure range is ordered, DO NOT change the Pressure Range Selection DIP switch settings.
Specifications lists Carrier’s standard model numbers.
Unidirectional and Bidirectional Mode
The DLP can operate in either unidirectional mode (0 X inWC) or bidirectional mode (± X inWC). Each unit could have up
to eight field selectable, uni or bidirectional ranges.
Caution
See Specifications for your DLP model’s maximum pressure.
DO NOT switch pressure range or output mode when POWER is ON. Make sure POWER to the unit is OFF. Failure to
do so WILL NOT ALLOW any new switch settings to take place.
Choose differential pressure range based on the expected differential pressure in your application. Move switches to
the correct positions and THEN POWER ON the transmitter.