Fig. 72 — Control Option “B,” Manual Fan Speed Control Typical Wiring Diagram
U1 U2
V1 V2
W1 W2
PE
VFD
BLK/134
YEL/135
BLU/136
GRN/137
BLK/140
RED/141
ORN/142
GRN/143
1
3
2
IFM
BLK/150
RED/151
ORN/152
GRN/153
L1
L2
L3
208/240v – 3Ø
GND
USE COPPER
SUPPLY WIRES.
BLK/101
240V
208V
YEL/102
COM
TRAN 1
RED/505
R
C
G
TB1
RED/505
BRN/502
BLK/504
CLASS 2
ABFR1
BRN/503
GRN/500
BRN/501
24 VAC
TRAN 1 IS FACTORY WIRED FOR 230V.
MOVE WIRE BLK/102 TO THE 208V
TAP FOR 208V APPLICATIONS.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
SCR
AI
GND
+10V
AI2
GND
AO
GND
+24
GND
DCOM
DI1
DI2
DI3
DI4
DI5
AI1
AI2
S1
VFD
RJ-45
BULKHEAD
PASSTHROUGH
BLU/508
VIO/506
BLU/507
4
7
KEYPAD/DISPLAY
NOTES:
1. This diagram represents the factory-installed electrical option with manual fan speed control using the VFD keypad mounted on outside of
unit.
2. Typical wiring is shown. For exact wiring, refer to the wiring diagram provided with the unit.
3. Field wiring includes power wiring (upper left hand corner) and low voltage control wiring (terminal block TB1).
4. Units ordered for 208V-240V voltage selection are factory wired for 240V. Field may rewire motor and transformer primary tap for operation at
208V.
5. Selection of field provided and installed electrical components is the responsibility of the installer, including branch circuit protection and
wiring.
6. To start the fan, connect R and G to energize fan relay FR1. Control fan speed using the keypad.
7. The control power (R and C at terminal block TB1) can be used to power a standard 24VAC thermostat, DX relay and up to 2 control valves.