Floor Mounting
Unit may be mounted on a housekeeping pad, floor or platform.
Vibration Isolators (Field Supplied)
If required, install isolators in the suspension rod system. Allow
clearance as needed between isolators and unit.
Discharge Air Arrangements (39SM Units)
MODULAR CONFIGURATIONS
The unit is shipped in two sections for easier handling and smaller
clearances. The two sections are manufactured and shipped to be
joined in one of the specific configurations shown in Fig. 24. If or-
dered incorrectly, the sections may be field-modified to achieve
one of the other configurations indicated in Fig. 24.
Fig. 23 — Unit Suspension
CAUTION
Make sure to allow enough elevation to permit construction of
the condensate trap. Failure to follow this caution may result in
unit damage.
IMPORTANT: Deviating from the factory-designed configura-
tions shown in Fig. 24 may result in improper or unacceptable
operation including inadequate airflow, fan vibration, fan noise,
or condensate carryover (blow-off).
(Field Supplied)
Airflow
Vibration Isolators
Ceiling - Recommended
Platform Mount
Ceiling - Alternate Crossbeam Mount
Ceiling – Alternate Suspension Rods
with No Mount