Carrier 39L handleiding

76 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 55 van 76
55
LEGEND
Table 21 — Electric Heater Data – 480-3-60 and 380-3-50
UNIT
SIZE
39L
HEATER
AREA
(sq ft)
NO. OF
CONTROL
STEPS
a
NOTE(S):
a. Standard control steps are listed under the Control Step heading. “Free” additional steps of control are optionally available when the number of subcircuits exceeds the
standard number of control steps.
HEATER
COIL
kW
NOMINAL
COIL FACE
VELOCITY
(fpm)
TEMP
RISE
(°F)
480-3-60 v-ph-Hz 380-3-50 v-ph-Hz
Total
FLA
MCA
b
b. MCA = 1.25 x FLA; for proper wire sizing, refer to Table 310-16 of the NEC.
No.
Sub-
Ckt
MOCP
Total
FLA
MCA
b
No.
Sub-
Ckt
MOCP
03 2.2 3
9.0 500 26 11 14 1 20 14 17 1 20
15.0 500 44 18 23 1 25 23 29 1 30
17.2 500 50 21 26 1 30 26 33 1 35
06 3.7 6
8.0 500 14 10 12 1 20 12 15 1 20
10.0 500 17 12 15 1 20 15 19 1 20
17.0 500 29 20 26 1 30 26 32 1 35
19.9 500 34 24 30 1 30 30 38 1 40
27.0 500 47 33 41 1 45 41 51 1 60
29.8 500 51 36 45 1
c
c. 2 control steps in this voltage.
45 45 57 1 60
36.0 500 62 43 54 1
c
60 55 68 2
c
70
08 5.1 6
15.0 500 19 18 23 1 25 23 29 1 30
25.0 500 31 30 38 1 40 38 48 1 50
35.0 500 44 42 53 1 60 53 67 2 70
39.9 500 50 48 60 2 70 61 76 2 80
43.2 500 54 52 65 2 70 66 82 2 90
51.0 500 64 61 77 2 80 78 97 2 100
10 6.2 6
15.0 500 15 1823 1 252329 1 30
25.0 500 26 3038 1 403848 1 50
39.9 500 41 4860 2 706176 2 80
47.3 500 49 5771 2 807290 2 90
51.8 500 53 6278 2 807998 2 100
59.8 500 62 72 90 2 100 91 114 2 125
12 7.3 6
19.9 500 17 2430 1 303038 1 40
29.8 500 26 3645 1 454557 1 60
39.9 500 35 4860 2 706176 2 80
43.0 500 38 5265 2 706582 2 90
51.8 500 45 6278 2 807998 2 100
72.0 500 63 87 108 2 110 110 137 3
d
d. 3 control steps in this voltage.
150
15 10.0 6
19.9 500 13 2430 1 303038 1 40
29.8 500 19 3645 1 454557 1 60
39.9 500 25 4860 2 706176 2 80
45.0 500 29 5468 2 706886 2 90
51.8 500 33 6278 2 807998 2 100
65.0 500 42 78 98 2 100 99 124 3 125
86.0 500 55 104 129 3 150 131 164 3 175
18 11.74 6
19.9 500 11 2430 1 303038 1 40
25.8 500 14 3139 1 403949 1 50
35.0 500 19 4253 1 605367 2 70
45.0 500 25 5468 2 706886 2 90
51.8 500 28 6278 2 807998 2 100
78.0 500 43 94 117 2 125 119 148 3 150
94.0 500 51 113 141 3 150 143 179 3 200
21 14.21 6
19.9 500 9 2430 1 303038 1 40
25.8 500 12 3139 1 403949 1 50
35.0 500 16 4253 1 605367 2 70
45.0 500 20 5468 2 706886 2 90
51.8 500 23 6278 2 807998 2 100
79.8 500 36 96 120 3 125 121 152 3 175
92.0 500 41 111 138 3 150 140 175 3 175
116.0 500 52 140 175 3 175
25 17.79 6
30.0 500 11 3645 1 504657 1 60
39.9 500 14 4860 2 706176 2 80
50.0 500 18 6075 2 807695 2 100
65.0 500 23 78 98 2 100 99 124 3 125
79.8 500 29 96 120 3 125 121 152 3 175
96.5 500 35 116 145 3 150 147 183 4
e
e. 4 control steps in this voltage.
200
110.0 500 39 132 166 3 175 167 209 4
e
225
145.0 500 52 175 218 4
e
225 221 276 5
f
f. 5 control steps in this voltage.
300
AHRI Air Conditioning, Heating and Refrigeration Institute
FLA Full Load Amps
kW Kilowatts
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection