Table 15 — Chilled Water Coil Circuiting Data
LEGEND
LARGE FACE AREA (39LA, 39LD)
COIL
TYPE
CIRCUIT
UNIT SIZE
03 06 08 10 12
Face Area (sq ft)
3.63 5.90 7.90 9.54 11.18
No.
Circuits
Connection
Size
b
No.
Circuits
Connection
Size
b
No.
Circuits
Connection
Size
b
No.
Circuits
Connection
Size
b
No.
Circuits
Connection
Size
b
4-ROW
Q 4 1-1/2 5 1-1/2 — — — — — —
H 8 1-1/2 10 1-1/2 12 1-1/2 12 1-1/2 12 1-1/2
F 16 1-1/2 20 1-1/2 24 2-1/2 24 2-1/2 24 2-1/2
D — — — — — — — — — —
6-ROW
H 8 1-1/2 10 1-1/2 12 1-1/2 12 1-1/2 12 1-1/2
F 16 1-1/2 20 1-1/2 24 2-1/2 24 2-1/2 24 2-1/2
D — — — — 36 2-1/2 36 2-1/2 36 2-1/2
LARGE FACE AREA (39LA, 39LD)
COIL
TYPE
CIRCUIT
UNIT SIZE
15 18 21
a
25
a
Face Area (sq ft)
14.91 17.71 21.60 25.00
No.
Circuits
Connection
Size
b
No.
Circuits
Connection
Size
b
No.
Circuits
Connection
Size
b
No.
Circuits
Connection
Size
b
4-ROW
Q — — — — — — — —
H 16 1-1/2 19 1-1/2 19 1-1/2 22 1-1/2
F 32 2-1/2 38 2-1/2 38 2-1/2 44 2-1/2
D — — — — 76 2-1/2 88 2-1/2
6-ROW
H 16 1-1/2 19 1-1/2 19 1-1/2 — —
F 32 2-1/2 38 2-1/2 38 2-1/2 44 2-1/2
D 48 2-1/2 57 2-1/2 57 2-1/2 66 2-1/2
SMALL FACE AREA (39LB, 39LC, 39LF)
COIL
TYPE
CIRCUITING
UNIT SIZE
03 06 08 10 12
Face Area (sq ft)
2.72 4.72 6.58 7.95 9.23
No.
Circuits
Connection
Size
b
No.
Circuits
Connection
Size
b
No.
Circuits
Connection
Size
b
No.
Circuits
Connection
Size
b
No.
Circuits
Connection
Size
b
4-ROW
Q 3 1-1/2 4 1-1/2 — — — — — —
H 6 1-1/2 8 1-1/2 10 1-1/2 10 1-1/2 10 1-1/2
F 12 1-1/2 16 1-1/2 20 2-1/2 20 2-1/2 20 2-1/2
D — — — — — — — — — —
6-ROW
H 6 1-1/2 8 1-1/2 10 1-1/2 10 1-1/2 10 1-1/2
F 12 1-1/2 16 1-1/2 20 2-1/2 20 2-1/2 20 2-1/2
D — — — — 30 2-1/2 30 2-1/2 30 2-1/2
8-ROW
c
H 6 1-1/2 8 1-1/2 10 1-1/2 10 1-1/2 10 1-1/2
F 12 1-1/2 16 1-1/2 20 2-1/2 20 2-1/2 20 2-1/2
D — — — — 40 2-1/2 40 2-1/2 40 2-1/2
SMALL FACE AREA (39LB, 39LC, 39LF)
COIL
TYPE
CIRCUITING
UNIT SIZE
15 18 21
a
25
a
Face Area (sq ft)
12.12 13.98 17.10 20.50
No.
Circuits
Connection
Size
b
No.
Circuits
Connection
Size
b
No.
Circuits
Connection
Size
b
No.
Circuits
Connection
Size
b
4-ROW
Q — — — — — — — —
H 13 1-1/2 15 1-1/2 15 1-1/2 18 1-1/2
F 26 2-1/2 30 2-1/2 30 2-1/2 36 2-1/2
D — — — — 60 2-1/2 72 2-1/2
6-ROW
H 13 1-1/2 15 1-1/2 15 1-1/2 — 1-1/2
F 26 2-1/2 30 2-1/2 30 2-1/2 36 2-1/2
D 39 2-1/2 45 2-1/2 45 2-1/2 54 2-1/2
8-ROW
c
H 13 1-1/2 13 1-1/2 — 1-1/2 — 1-1/2
F 26 2-1/2 30 2-1/2 30 2-1/2 36 2-1/2
D 52 2-1/2 60 2-1/2 60 2-1/2 72 2-1/2
NOTE(S):
a. Sizes 21-25 have 2 coils.
b. Connection sizes are MPT - inches.
c. Not available on 39LB units.
D — Double Circuit
F — Full Circuit
H — Half Circuit
Q — Quarter Circuit