29
(Press ) to save the configuration and return to the Sub
list menu.
4. Use the UP or DOWN keys to highlight SET TIME and press
SEL (Press ). Use the UP or DOWN keys to change
the hours and minutes. Press OK (Press ) to save the
configuration and return to the Clock Set menu.
5. Use the UP or DOWN keys to highlight TIME FORMAT and
press SEL (Press
). Use the UP or DOWN keys to
change the parameter setting. Press OK (Press ) to
save the configuration and return to the Clock Set menu.
6. Use the UP or DOWN keys to highlight SET DATE and
press SEL (Press
). Use the UP or DOWN keys to
change the day, month, and year. Press OK (Press ) to
save the configuration and return to the Clock Set menu.
7. Use the UP or DOWN keys to highlight DATE FORMAT
and press SEL (Press
). Use the UP or DOWN keys to
change the parameter setting. Press OK (Press ) to
save the configuration and return to the Clock Set menu.
8. Press BACK (Press ) twice to return to the main menu.
I/O SETTINGS MODE
Use the I/O Settings mode to view and edit the I/O settings.
To configure the I/O settings, perform the following procedure:
1. Select MENU (Press ). The Main menu will be
displayed.
2. Use the UP or DOWN keys to highlight PRIMARY SETT.
on the display screen and press SEL (Press
). The Sub
list will be displayed.
3. Use the UP or DOWN keys to highlight ADVANCED
OPTIONS/FUNCTIONS. on the display screen and press
SEL (Press
). The Sub list will be displayed.
4. Use the UP or DOWN keys to highlight I/O SETTINGS on
the display screen and press SEL (Press
). The I/O Set-
tings parameter list will be displayed.
5. Use the UP or DOWN keys to highlight the desired I/O set-
ting and press SEL (Press ).
6. Use the UP or DOWN keys to select the parameter to view.
Press OK (Press
).
7. Use the UP or DOWN keys to change the parameter setting.
Press SAVE (Press
). to save the configuration. Press
CANCEL (SOFT KEY 1) to keep the previous value. Any
modifications that are not saved will not be changed.
8. Press BACK (Press ) twice to return to the main menu.
VFD Diagnostics
The drive detects error situations and reports them using:
1. Status LED on the control panel
2. Control panel display
3. The Fault Word and Alarm Word parameter bits
The form of the display depends on the severity of the error. The
user can specify the severity for many errors by directing the drive
to ignore the error situation, report the situation as an alarm, or re
-
port the situation as a fault.
FAULTS (RED LED LIT)
The VFD signals that it has detected a severe error, or fault, by:
1. Enabling the red LED on the drive (LED is either steady or
flashing).
2. Setting an appropriate bit in a Fault Word parameter.
3. Overriding the control panel display with the display of a
fault code.
4. Stopping the motor (if it was on).
The fault code on the control panel display is temporary. Pressing
the MENU, (Press
). buttons removes the fault message.
The message reappears after a few seconds if the control panel is
not touched, and the fault is still active. See Table
8 for a list of
fault codes.
ALARMS (GREEN LED FLASHING)
For less severe errors, called alarms, the diagnostic display is advi-
sory. For these situations, the drive is simply reporting that it had
detected something unusual. In these situations, the drive:
1. Flashes the green LED on the drive (does not apply to alarms
that arise from control panel operation errors).
2. Sets an appropriate bit in an Alarm Word parameter.
3. Overrides the control panel display with the display of an
alarm code and/or name.
Alarm messages disappear from the control panel display after a
few seconds. The message returns periodically as long as the
alarm condition exists. See Table
8 for a list of alarm codes.
CORRECTING FAULTS
The recommended corrective action for faults is shown in the
Fault Listing Table
8. The VFD can also be reset to remove the
fault. If an external source for a start command is selected and is
active, the VFD may start immediately after fault reset.
To reset a fault indicated by a flashing red LED, turn off the power
for 5 minutes. To reset a fault indicated by a red LED (not flash-
ing), press RESET from the control panel or turn off the power for
5 minutes. Depending on the value of parameter, digital input or
serial communication could also be used to reset the drive. When
the fault has been corrected, the motor can be started.
CORRECTING ALARMS
To correct alarms, first determine if the alarm requires any correc-
tive action (action is not always required). Use Table 8 to find and
address the root cause of the problem.
If diagnostics troubleshooting has determined that the drive is de-
fective during the warranty period, contact Carrier.
CONTROL PANEL CLEANING
Use a soft damp cloth to clean the control panel. Avoid harsh
cleaners which could scratch the display window.
BATTERY REPLACEMENT
A battery is only used in assistant control panels that have the
clock function available and enabled. The battery keeps the clock
operating in memory during power interruptions. The expected
life for the battery is greater than ten years. To remove the battery,
use a coin to rotate the battery holder on the back of the control
panel. Replace the battery with type CR2032.