Carrier 39L handleiding

76 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 17 van 76
17
LEGEND
Fig. 11 — Unit Rigging Details
Fig. 12 — Unit Support Details, Overhead Suspension
HEATING COILS
Hot Water 1/2 in. OD Tube, U-Bend (1, 2 Row)
Face Area (sq ft) 2.72 4.72 6.58 7.95 9.32 12.12 13.98 17.1 20.5
Number Tubes/Face 12 16 20 20 20 26 30 30 36
Finned Tube Length (in.) 26.1 34.0 37.9 45.8 53.7 53.7 53.7 65.5 65.5
Steam 1-in. OD Tube, (1 Row)
Face Area (sq ft) 2.13 4.18 6.22 7.53 8.85 11.06 13.28 16.2 18.9
Number Tubes/Face 4688 8 10121214
Finned Tube Length (in.) 25.5 33.4 37.3 45.2 53.1 53.1 53.1 53.1 64.9
NOTE(S):
a. See Table 2 for section weights and dimensions.
b. Coils have 14 aluminum fins per inch on copper tubes.
Table 3 — Additional Component Data
a
(cont)
39L UNIT SIZE 03 06 08 10 12 15 18 21 25
DX Direct Expansion
FPI —Fins Per Inch
SPREADER
BAR
LIFTING
BRACKET
NOTE(S):
Lift in one piece. Use slings and spreader
bars at each lifting bracket.
LIFTING BRACKET
DETAILS
7/16 IN. DIAM. HOLE
VIBRATION ISOLATORS
(FIELD SUPPLIED)
SUSPENSION ROD
(FIELD SUPPLIED)
SUSPENSION CHANNEL
(FACTORY-SUPPLIED OPTION)
MOUNT UNIT TO SUSPENSION CHANNELS
THROUGH 7/16
PROVIDED IN LIFTING BRACKET
IN. DIAM. HOLES
FACTORY-SUPPLIED BOLTS
CONNECTING SUSPENSION
CHANNEL SECTIONS
OVERHEAD SUSPENSION
a3 - 450