H03846‐00.A1.EN–2012/10 14
4.Maintenance
4.1Maintenanceinstructions
Ageneralserv icingoftheapplianceisrecommendedbothwhenwinterizingandwhenrestartinginorder
toensuretheproperoperationofyourheatpump,topreserveitsperformanceandtopreventpotential
failures.
Servicingcostswillbebornebytheuser.
Appliancepoweredoffandu npluggedfrompowersupply!
Theappliancemusthavefiltersfittedwhenoperating.
4.1.1Monthlychecks
checkvisuallythatthecondensationisdrained.
checkforclogginginthefilter:
‐washthefilterwithwarmsoapywater,
‐rinseitabundantlyanddryit,
‐replaceitifnecessary.
4.1.2Quarterlychecks
Check the tightness of the centrifuge fan belt: push the belt down between the two pulleys, it should yield
about1cm.
4
.
1.3Annualchecks
checkthattheelectriccableconnections,contactorsarecorrectlytightened,
checkthateachcommandrelay,powerswitchandelectronicprotectiondeviceisoperational,
Onthree‐phaseappliance,viathephasecontroller(KA4),anymodificationoftheorderofphasesonthe
distributionnetworkorontheexistingelectricalinsta llationisdetected.Theappliancethengoesintofault
mode(LedA1andA3ON,andorangelightOFFforKA4),referon§5.1.
check the adjustment and operation of the Hygro Control and the water condenser thermostat if necessary
cleanthedustinsideitusingajetofair,
cleanthewholeunitwithaslightlydampcloth,
checkthecleanlinessofthecondensationdrainagetrayandtube,
checktheco
nditionoftheinsulating foamonthetechnicalcompartment.
check the movementof the centrifuge ventilator blades (the bearings are greased permanently andneed no
maintenance),
checkthatthebatteriesareclean.Ifnecessary,cleanthemusingahardsilkbrush,avacuumcleanerorajetof
compressed air.Rinse usi
ngcold waterunderpressuretaking caretoavoidsplashing wateron theve ntilator
motor.
4.2Additionalrecommendations
inrelationtothePressureEquipmentDirective(PED‐97/23/CE)
4.2.1Installationandmaintenance
theunitmaynotbeinstall edclosetocombustiblematerials,ortheairductinletofanadjacentbuilding.
withsomedevices,itisessentialtofitprotectiongridsiftheunitisinstalledinanareawithuncontrolledaccess.
during installation, troubleshooting and maintenance, pipes may not be used as steps: the pipe coul
d break
undertheweight,spillingrefrigerantandpossiblycausingseriousburns.
whenservicingtheappliance,thecompositionandstateofheatcarryingfluidmustbechecked,aswellasthe
absenceofanyrefrigerant.
duringtheannualunitsealingtestinaccordancewithapplica
blelegislation,thehighandlowpressureswitches
must be checked to ensure that they are securely fastened to the coolant circuit and that they cutoff the
electricalcircuitwhentripped.
duringmaintenancework,ensureth erearenotracesofcorrosionoroilaroundcoolingcomponents.
before begin
ning work on the cooling circuit, stop the device and wait for a few minutes before fitting the
temperatureandpressuresensors.Someelementssuchasthecompressorandpipingmayreachtemperatures
inexcessof100°Candhighpressureswiththeconsequentriskofseverescalding.