Zodiac CAE Ducted handleiding
Handleiding
Je bekijkt pagina 14 van 26

H03846‐00.A1.EN–2012/10 13
3.5.2Hotwaterbattery
Supply the battery with hot water at 50 °C minimum from the heat source (boiler, heat pump, geothermal
energy,solarheating),installationmustbecarriedoutbyaqualifiedtechnician,usingacirculator(notsupplied)
whichwillbepoweredbyterminalsC‐Contheelectricalterminalboard.
Insulate the hot water battery hot water pipes between the heat source and the appliance (for the
purposeoflimitingcalorieloss).
connectiontoaZPCEdoublecircuitgasboiler:connecttheterminals3‐6oftheterminalboard,toterminals3‐6
oftheboilerterminalboard,
Terminals3‐6canalsoensureaheatsourcecontrolfunction(see§2.6.2).
adjust thethermostat between to 26 and 28°C (maximum 30°C), in general set the air temperature 1 to 2°C
higherthanthepoolwatertemperature,
If your pool has a cover (shutter or bubble sheet type, etc.), you can lower the room temperature (by
adjusting the thermostat to about 20°C) when it is in place andraise the pool hall temperature before
removingthecover.
apost‐ventilationrunsfor3minuteswhenthereferencetemperatureisreducedonthether mostatlocatedin
thepoolhall(withthe“VI/VP”switchon“VI”,withoutanydehumidificationordefrostingcyclesinprogress):
checkthatthecirculatorstops.
Warning‐lowtemperature:ifthedeh umidifierhotwaterbatteryisnotsuppliedbyaboiler,butbyan
aero‐thermal ora geothermalsystem, theheatingcircuitwater willbeat amaximum temperature of
50‐40°C.Thepowerofthebatterywillthenbeconsiderablylower(3to4timesless)thanthenominal
power given for water at90‐70°C. If the power of the battery islower than the heating needs of the
room,planforadditionalheatingbyradiator,heatedfloororfanconvector.
3.5.3Titaniumwatercondenser
connecttheintakeandoutputtothefilterusingaby‐pass,accordingtothemarkings
ontheappliance(beforethepoolwatertreatmentsystem),see§2.7.2,
Adjustingtheby‐passforthewatercondenser:
- openvalvehalfway
- openvalvesandcompletely
plan to shunt th
e filter clock from the S‐S terminals on the appliance electrical
terminalboard,
inthecaseofa hydraulicconnectionwithpumpthatisindependentofthefiltering
system, plan to power this pump using theP‐P terminals ontheappliance terminal board(maximum power:
60Wwith230VAC,otherwiserelaythepowersupplyfromanextraele
ctriccontactor),
startingup:setthe“TH”digitaldisplaythermostatfittedinsidetheelectricalbox:
press “SET” to display the current reference value (factory preset at 27°C, thus the
thermostatoutputwillbeactivatedwhenthepoolroomtempera
turewillrisesabove29°C
anddeactivatedifthetemperaturedropsbelow27°C):the“out1”LEDblinks(hysteresis=
2°C),
- press or(possiblerangevalues:25°Cminimumand45°Cmaximum),
- press“SET”,ordonotoperatefor15seconds,toconfirm.
checkthatthefilterpu
mpstartswhentheadjustmentofthisdigitaldisplaythermostatis
reducedtobelowthesurroundingtemperature.
checkthatthe«VCA»indicatorlightswhenthethermostatreferencevalueislowered.Bydefault,checkthat
thefilterpumpisoperationalandsufficientlyirrigatesthewater condenser(seeby‐pass adjustment).
when the wat
er condenser option is operational (VCA indicator on), check that the «EV» solenoid valve is
poweredfromterminalsEandV(230Vac)ontheapplianceterminalboard.Ifthisis notthecaseadjusttheby‐
pass so that there is a sufficient flow of water in the cond
enser to activate the flow controller fitted at the
output of the water con denser (this safety device is connected between terminals I and D, see the electric
wiringdiagramintheappendix).