Zodiac CAE Ducted handleiding

26 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 13 van 26
H0384600.A1.EN2012/10 12
Thisoperationmustbeonlybecarriedoutbyaqualifiedprofessional.
Thephaseordercontrollerprotectsthecompressor.It’sforbiddentoinvertphases:
onthepowercontactor(KM1and/orKM2)
onthecompressor
ontheventilator
onthethermalprotection
onthephaseordercontroller
Activatetheswitchesdependingonneedsandoptions(s):
Trigger(s)/switches IG ID ICE/ICB ICC
Dehumidifier X X
Dehumidifier+airheating* X X X
Dehumidifier+watercondenser X XX
Dehumidifier+airheating*+watercondenser X X X X
* extraheatingorhotwaterbatteryoption
startupanappliancewithoptions,seealso§3.5,
setthehumidity andtemperature on the Hygro Controlso that it triggers dehumidifying and / or airheating
(optional),see§2.6.4.
Whenthe“ECP600”regulatorisswitchedonventilationisactivefor5minutes.Thisalsooccursifthe
appliance is poweredon andthe “on/off”switch ofthe HygroControl delivered withthe applianceis
used.
3.3Checks
IntheHygroControlcomfortmodel(see§2.6.4)
checkthathotairiscomingoutoftheblowergrates,
checkthattheapplianceisdrainingcondensation.
3.4Adjustingtheductnetwork
Setthe air flow by adjusting the grate dampers (recommended speed≈metre/second) identically on all the
blowergrates.
3.5Optionsstartingup
Theheatingoptionsareoperationalfrom4°Csurroundingairtemperature.
3.5.1Extraheating
starting up Hygro Control and adjust the thermostat to between 26 and 28°C (maximum 30°C), in general
chooseanairtemperature1to2°Chigherthanthepoolwatertemperature,
ifyour poolhasacover(shutterorbubblesheettype,etc.),youcanlowertheroomtemperaturewhenit
is in place (by adjusting the thermostat to about 20°C) and raise the pool hall temperature before
removingthecover.
checkthatwiththe“VI/VP”switchon“VI”,andnodehumidificationordefrostingcyclesinprogress:
- the fan stops operating, after postventilation of 3 minutes when the reference room temperatureon the
poolroomthermostatislowered,
- intheeventofabnormaloverheating,theapplianceshutsdowntheheat
ingoptionautomatically,byshutting
offtheheatingelementsandkeepingtheventilationoperational(foraslongasaheatingrequestisactive).
Thissafetydevicehastwolevelsoftriggering:
1) by “THS” safety thermostat if the T°C is > 65°C (it is automatically
reset),
2) ifthetemperaturecontinuestoincrease,thesecondpositive“THSM”
safetyther
mostatputstheapplianceintosafetymode.
=> reset it manually (with power off), after having checked that the
appliance air flow is correct (with the “VI/VP” switch on “VP”), that
the grates are notobstructed, that the filter is not clogged, and the
fanisnotdef