BUILDING AUTOMATION
4.5.1.2 Parameter window “Cx: Auto.”
The parameter window “Cx: Auto.” setting interface is shown in Figure 4.16. Here, the automatic function and sun protection operation are mainly set. The
louver actuator positions the louver based on the intensity of the light sensed by the illuminance sensor. For example, when the sun is very weak or there
is no light coming through the window, the blinds/curtains can be raised to allow as much light as possible to enter the room. If there is strong sunlight
outside the window, you can lower the blinds/curtains and adjust the louver angle so that direct light does not penetrate into the room, while the shutters
are partially open to allow some diffuse light to enter the room.
Fig. 4.16 Parameter window “Cx: Auto.”
Parameter “Function automatic”
Set whether to activate the automatic control operation, that is, the automatic sun protection function. Options:
Inactive
Active
When the option is “Active”, the following parameters are visible, the objects “Enable auto. control”, “Sun operation”, “Sun: blind/shutter position
0…100%” and “Sun: slat adj. 0…100%” visible.
When the object “Enable auto. control” receives the message “1”, the operation of the blinds switches to automatic operation; when the object “Enable
auto. control” receives the message “0” or the user sends a direct move command (such as Up/down, moving to a certain position, etc. These commands
cause the blinds to move; if the scene is saved, these commands that are not directly moved will not cause the operation state to exit the automatic
operation), and the operation state exits the automatic operation. Switch to normal operation. The priority of normal operation and automatic operation
is the same, but they cannot happen at the same time.
Note: After the automatic operation exits, the message “1” must be received again via the object “Enable auto. Control” or the duration of the
automatic activation has elapsed (see the parameter “Enable auto. Control after [10...6000min]” below for details).
Description), in order to enter the automatic operation again.
Parameter “Object value of ‘Enable auto. control’ after bus voltage recovery”
This parameter defines the initial value of the object “Enable auto. control” after a bus reset. Options:
“0” (Disable auto. control)
“1” (Enable auto. control)
When the option is “0”, the initial value of the object “Enable auto. Control” is 0, indicating that automatic operation is not enabled after the bus reset;
When the option is “1”, the initial value of the object “Enable auto. Control” is 1, indicating that automatic operation is enabled after the bus reset.
Parameter “Automatically enable for auto. control”
This parameter defines whether automatic reactivation can be performed after the automatic operation exits via normal operation or the object “Enable
auto. control”. Options:
No
Yes
Select “yes” and the following parameters are visible.
Parameter setting description in the ETS