BUILDING AUTOMATION
Parameter “Duration of slat adjustments [10…250]*10ms”
This parameter sets the Shutter angle adjustment time, that is, the time when the louver angle is adjusted when a command to adjust the angle up or
down is received. The shorter the time, the more accurate the angle is adjusted.
After the shutter moves up, the shutter angle is usually open. If the shutter is lowered now, the louver angle is first closed and then the shutter moves
downward. If the blinds are now rising again, the louver angle first opens and then rises. (As shown below)
Blind
raised
Blind
lowered
Parameter “Total travel time of slat 0…100% in [10…250]*10ms”
Here shutter angle adjustment is provided from the fully closed state to the fully opened state of the overall travel time required, the current position of
the shutter during angular adjustment is determined by this parameter. Therefore, it is very important to measure and set the total travel time of the shut-
ter adjustment as accurately as possible. Especially in the case of “Slat position via a 1 byte value” and “Status response”, the only way to accurately
calculate the current position of the louver is.
When the louver angle is adjusted by the object “Slat adj./Stop”, the maximum number of times the louver angle needs to be adjusted from the fully closed
state to the fully open state = the total travel time of the louver angle adjustment / the one adjustment time. The adjustment time of one time is set by the
previous parameter. The shorter the set time, the more the adjustment will be, and the more accurate the angle.
Parameter “Pause on change in direction [5…255]*20ms”
This parameter is used to set the time to pause when the direction of movement or angle adjustment is changed. The pause time when the direction is
changed needs to be considered in conjunction with the technical data provided by the manufacturer of the drive unit to obtain an appropriate value.
Steering can prevent the blind drive from damaging when it suddenly changes direction, extending the life of the drive.