BUILDING AUTOMATION
Shutter type (without louvers)
Fig. 4.15 Parameter window “Cx: Drive”
Parameter “Total travel time [20…50000]*0.1s”
This parameter sets the time required for the shutter to move the total stroke.
The total travel time is the time it takes for the blind to move from the highest position to the lowest position (as shown below). When the louver actuator
receives a command to move up or down, the louver moves according to the required direction until the louver receives a command to stop moving, or
until it moves to the highest or lowest position, then the louver passes through itself The limit switch turns the motor off. If the blinds are closed by the
motor, the corresponding output of the connected actuator is still closed and the output connection will only be disconnected if the set total travel time
has elapsed.
Shutter UP
Upper limit
switch
Lower limit
switch
Total travel
time
Shutter
DOWN
Note: The current position of the Shutter during operation can also be determined with the help of the total move time. It is therefore important
to measure and set the total move time as accurately as possible, particularly if the functions “Move to position via a 1 byte value” and “Status
response” are used. Only then is it possible to calculate the current position of the Shutter precisely.
Parameter “Delay time from switch-on to moving [0..200]*10ms”
This parameter sets the delay time for the Blinds/Shutter to start running, that is, after receiving the control command and closing the relay contact, how
much time delay is required before the curtain starts to slide, that is, the start buffer time of the motor. Options:
0..200
The setting of this parameter needs to be considered in conjunction with the starting technical characteristics of the curtain.
Parameter setting description in the ETS