BUILDING AUTOMATION
Parameter “If bus failure, contact is”
The output can adopt a defined status after the bus voltage failure via this parameter. Options:
Unchange
Open
Close
When selecting “Unchange”, the contact will not change when bus power on;
When selecting “Open”, the contact will be opened when bus power on;
When selecting “Close”, the contact will be closed when bus power on.
Parameter “After downloading, contact is”
This parameter set the contact position of the output after downloading. Options:
Open
As bus recovery
When selecting “Open”, the contact is open after application downloading;
When selecting “As bus recovery”, the contact will action according to the setting of parameter “If bus recovery, contact is” after application downloading.
Parameter “Object Value of “ switch” after bus recovery”
This parameter will be visible when enabling the logic function “input 0” to define the default value of the communication object “Switch” after bus voltage recovery,
which can be “0” or “1”. Options:
0
1
Parameter “Set the reply mode of switch status”
This parameter defines how to respond the current switch status to the bus. There are two options to select. Options:
Respond after read only
Respond after change
If selecting “Respond after read only”, the status telegram will not be sent out until receiving a read request telegrams via the object “reply switch status” from
the bus.
If selecting “Respond after change”, when switch status of the channel changes, object “switch status” will immediately send the current report telegram to the
bus.
Parameter “Object value of switch status :”
Options:
0=contact close; 1=contact open
1=contact close; 0=contact open
When setting “0=contact close; 1=contact open”, the value of object “switch status” is 0 indicates the contact of the relay will be closed; when is 1, indicates the
contact of the relay will be closed will be open.
When setting “1=contact close; 0=contact open” indicates the opposite meaning.
Note: After programming or system reset, the switch status is determined, the object “switch status” will send status messages to the bus; if not, it
will not be sent.
Parameter “Contact position if tele. Value is ‘1’(‘0’ is opposite of ‘1’ if changed) ”
This parameter defines the contact position when switch on the switch, which will be triggered by the communication object “switch”. When enabling “input 0”
in the logic function, it will use the communication object “switch” to modify the value of “input 0”, rather than triggering the switch operation. In this case, this
parameter setting is no significance. Options:
Open
Close
When select “Open”, the contact position is open, when receive telegram “1”, the contact will be open; when receive telegram “0”, the contact close;
When select “Close”, the contact position is close, when receive telegram “1”, the contact will be closed; when receive telegram “0”, the contact open.
Note: When the logic function input 0 enables, the object “switch” used as input of input 0, the operation of general switch will become invalid.