Step 1. Allow more than10seconds toelapse after removing thepowercords fromthe VX-3000DS' rear-
mounted AC inlets (IN1 and IN2).
Step 2. Insert the positive battery cable into the VX-3000DS' rear-mounted BATTERYPOWER IN positive
terminalfromthebottomsideoftheconnector,thentightentheterminalscrewwithaatscrewdriver.
Note
Neverconnectthenegativecablersttoavoidbattery short-circuitthatoccursifthepositivecable
should contact the unit chassis or equipment rack.
Step 3. Connect the negative battery cable to the negative terminal in the same manner as Step 2.
VX-3000DS
Tightening torque: 6 – 8 Nm
3
2
Cable cross
sectional area
16 mm
2
25 mm
2
35 mm
2
50 mm
2
180 cm
280 cm
400 cm
570 cm
AWG 6
AWG 4
AWG 2
AWG 0 (AWG 1/0)
80 cm each
130 cm each
190 cm each
275 cm each
20 cm
20 cm
20 cm
20 cm
Length (2 mΩ)AWG
Example of wire length
Cable A, Cable C Cable B
VX-3000DS’ Battery connection terminals
Battery terminals
6 – 8 Nm
4.1 – 5.6 Nm (M6)
8.2 – 5.6 Nm (M8)
• Usethebatteryconnectioncablesasshortinlengthandaslargeindiameteraspossible.
Battery connnection terminals
Battery
Cable A
Cable C
Cable B
Battery
VX-3000DS
TEMPERATURE
SENSOR
24V(16-25V)
POWER OUT
MAX 0.3A
IN
OUT
DS LINK
• Totalresistanceofthebatteryconnectionpathshouldbelessthan4mΩ,whichincludesresistanceofallof
wire, terminal, fuse, and terminal points.
For reference, refer to each resistance as follows.
Resistanceofterminal,fuse(ifprovided): 1–2mΩ
Resistanceofterminalpoint: 0.1–0.5mΩ
• Tightenthebolts,nuts,andscrewsoftheunit'sbatteryconnectionterminalsandbatteryterminalswiththe
torque as shown below.