Chapter 3: Maintenance and Component Installation
Release Tabs
Figure 3-8. Replacing a Fan
System Fans
The system includes ve 8-cm fans, which are mounted on the rear of the chassis to provide
cooling for the nodes. These fans are hot-swappable and designed to be easily changed,
with no tools required. Each fan cools a pair of adjacent nodes (see Nodes section at the
beginning of this section). Replacement fans may be ordered directly from Supermicro.
Replacing a Fan
1. Inspect the fans or use IPMI to determine which fan must be replaced. Do not run the
server for an extended period of time with a fan removed.
2. Squeeze both release tabs simultaneously on the fan to be removed.
3. Pull the fan module away from the chassis.
4. Place the replacement fan into the vacant space and push in until you hear a click
indicating the fan is fully seated in the chassis.