• If the single-core cables exceed 400 meters, log into the Web UI of Logger4000, on the
MPLC page, set the PLC master node's frequency to Band2 or Band3.
Requirements for parallel-pair cables
When using parallel-pair cables, to ensure MPLC communication quality, the length
difference between the two sets of cables must not exceed 5 meters. For single-core
parallel-pair, the requirements for both sets of cables and the frequency band settings are
the same as mentioned above.
Figure 6-14 Parallel-pair cables layout
PLC cable installation requirements
• The distance between low-voltage AC cables and medium-voltage AC cables should
meet the following requirements:
- Maintain a minimum horizontal distance of 0.5m between low-voltage AC cables and
medium-voltage AC cables when laid parallel.
- If two cables are laid in a crossing manner, the angle of crossing should be between
60° and 120°, and the vertical distance should be no less than 0.5m.
System Manual6 Electrical Installation
50