Table 6-4
Paramet
er
Description Cable Specification
D2
Length of PLC cable
from MVS to inverter
If using multicore AC cable, the length
should be ≤990m.
If using single-core AC cable,the single-
core cable length should be ≤790m.
If using parallel-pair cables, the length
requirements are the same as above.
Requirements for PLC wiring from MVS to inverter
General requirements
The cable connecting the box-type transformer and the inverter can be a multicore AC
cable, single-core AC cable, or parallel-pair cables, depending on the specific requirements
of the project.
To ensure communication quality, the use of multicore cables is recommended.
The cable should be laid in cable trenches, cable ducts, or conduits.
The cables should be laid parallel without any knots or twists.
For three-phase single-core cables, they should be fixed every 1 meter and arranged in
a "triangular" shape.
In this scenario, the cables are not easily bent. It is recommended to tie them
separately at positions 10cm before and after the bend.
System Manual 6 Electrical Installation
49