Table 6-4
Paramet
er
Description Cable Specification
D2
Length of PLC cable
from MVS to inverter
• If using multicore AC cable, the length
should be ≤990m.
• If using single-core AC cable,the single-
core cable length should be ≤790m.
• If using parallel-pair cables, the length
requirements are the same as above.
Requirements for PLC wiring from MVS to inverter
General requirements
The cable connecting the box-type transformer and the inverter can be a multicore AC
cable, single-core AC cable, or parallel-pair cables, depending on the specific requirements
of the project.
To ensure communication quality, the use of multicore cables is recommended.
• The cable should be laid in cable trenches, cable ducts, or conduits.
• The cables should be laid parallel without any knots or twists.
• For three-phase single-core cables, they should be fixed every 1 meter and arranged in
a "triangular" shape.
In this scenario, the cables are not easily bent. It is recommended to tie them
separately at positions 10cm before and after the bend.
System Manual 6 Electrical Installation
49