Only AC cables under the same box-type transformer can be laid in the same cable
trench.
When using different box-type transformers, the distance between the low-voltage side
cable trays should meet the following requirements:
- Maintain a minimum horizontal distance of 0.5m between cable trays from different
box-type transformers.
- If two cables are laid in a crossing manner, the angle of crossing should be between
60° and 120°, and the vertical distance should be no less than 0.5m.
Figure 6-15 Vertical crossing distance between PLC cables
Choose an AC cable equipped with PLC communication, wiring method reference 6.6.2
Procedure.
System Manual 6 Electrical Installation
51