Sungrow MVS4500-LV handleiding
Handleiding
Je bekijkt pagina 33 van 97

• The MVS is recommended to be positioned in a place at least 100mm above
the ground.
• if the LV cabinet bottom sits at a height of ≥200mm to the ground, it is
recommended to build a platform on the foundation to facilitate O&M.
5.3.3 Fixing the MV Station(optional)
The position for installing L-shape angle steel is reserved at the bottom of the container.
Preparing Installation Tools
The following tools may be used in installing the L-shape angle steel:
N
o.
Name Resource
1 Marker Beyond the scope of delivery
2 φ22 percussion drill Beyond the scope of delivery
3 Angle steel In the scope of delivery
4
M16×150 expansion
bolts
Beyond the scope of delivery
5 M16×50 screw In the scope of delivery
Installation Method
Other Precautions
NOTICE
A drainage system should be designed on the installation site to prevent the MV Station
from being immersed in water during heavy rainfalls.
System Manual5 Mechanical Installation
28
Bekijk gratis de handleiding van Sungrow MVS4500-LV, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Sungrow |
| Model | MVS4500-LV |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 9056 MB |







