The MVS is recommended to be positioned in a place at least 100mm above
the ground.
if the LV cabinet bottom sits at a height of ≥200mm to the ground, it is
recommended to build a platform on the foundation to facilitate O&M.
5.3.3 Fixing the MV Station(optional)
The position for installing L-shape angle steel is reserved at the bottom of the container.
Preparing Installation Tools
The following tools may be used in installing the L-shape angle steel:
N
o.
Name Resource
1 Marker Beyond the scope of delivery
2 φ22 percussion drill Beyond the scope of delivery
3 Angle steel In the scope of delivery
4
M16×150 expansion
bolts
Beyond the scope of delivery
5 M16×50 screw In the scope of delivery
Installation Method
Other Precautions
NOTICE
A drainage system should be designed on the installation site to prevent the MV Station
from being immersed in water during heavy rainfalls.