1. Introduction
The access of Diesel Generator is in the off-grid scenario.
The system stores PV energy in batteries during daytime, provided that there is energy
surplus and supplies power to loads when the PV energy is insufficient or there is no PV
energy at night.
When the battery power drops to a certain value, and a power outage occurs in the grid,
the system will start the generator to power the load and charge the battery.
Generator’s work logic is as follows:
(i)when the grid is not available and the battery is discharged to GEN_Start_SOC, the
generator starts to power the load and charges the battery to GEN_Exit_SOC, then the
generator stops.
(ii)If the load power>the generator rated power in (i), the battery will be discharged to
power the load until Overdischarge_SOC, then generator may shutdown due to
overload and the load will be powered off.
(iii)If the generator fail to start in (i), the battery will be discharge to Overdischarge_SOC,
then the load power off.
(iv)If the system goes into the end of (iii), the battery will not discharge before it is
charged to Overdischarge_SOC+ Overdischarge_Hysteresis_SOC (set by user).
1.6.3 System with generator
Figure 1.5 Typical off-grid scenario diagram (Generator on Gen port)
SolisCloud
APP Web
Backup Load
Generator
Battery
PV Module
Phone
Power Line
Signal Line
Hybrid Inverter
07
Bekijk gratis de handleiding van Solis S6-EH3P10K02-NV-YD-L, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.