User Manual
1. Introduction
Figure 1.6 Typical off-grid scenario diagram (Generator on ATS)
SolisCloud
APP Web
Backup Load
Grid Load
CT/Smart Meter ATS Generator
Phone
Battery
PV Module
Hybrid Inverter
Power Line
Signal Line
NOTE:
In single system, a diesel generator can be connected via both AC-Gen port
and ATS. If via AC-Gen port, it will only supply power to the backup load ;
if it is necessary to supply power to the grid side, it is recommended that the
generator be connected through ATS.
In parallel-system scenarios, connecting a diesel generator via ATS is
recommended.
When the system is connected to the generator, it cannot be connected to a
grid-tied inverter, because of a risk of damaging the generator.
It is recommended that the generator power be greater than the backup load
power.
If the generator is connected through an ATS on the grid side, then CT or
smart meter is required.
CAUTION:
When the generator is connected, it is essential to correctly select the
generator position on the APP, otherwise it may cause system failure or
damage to the generator.
08