Sime Murelle 70 Box ErP handleiding

56 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 12 van 56
12
Fig. 11
2.9.1 Wiring diagram single generator (fig. 11)
KEY
F1-2 Fuse (4 AT)
TRA Ignition transformer
PI Pump high efficiency
V Fan
EA Ignition electrode
ER Ionisation electrode
EV1-2 Gas valve coil
TS Safety thermostat
SF Exhaust temperature sensor
TFU Thermal fuse
SM Flow temperature sensor
SR Return temperature sensor
TPA Pressure transducer
TA1 Zone 1 environment thermostat
JP1 Selection TA2 or 0-10 VDC
TA2 Zone 2 environment thermostat
SB/SA Antifreeze siphon sensor
CR Remote control
SIME HOME (optional)
SE External sensor (optional)
OP Programming clock (optional)
AR Remote alarm
VZ Zone valve
AUX Auxiliary connection
PA Water pressure switch
RS-485
CASCADE
board
NOTE: Connect TA1 to the clamps 7-8
after having removed the bridge.
For BMS (0-10v dc) operation:
- Remove the jumper JP1 and ensure that TA1 link is fitted
- Connect the positive signal at terminal 10 of CN6
- Connect the negative signal at terminal 4 of the CN4.
RS-485
(24 VAC)
OP
(24 VAC)
SE (5 VDC)
SB/SA
(5 VDC)
TA1 (24 VRAC)
TA2 (24 VRAC)
SR (5 VDC)
SF (5 VDC)
SM (5 VDC)
TS (24 VDC)
KIT
SICUREZZE
INAIL
0...10VDC
CD. 6328950
CD. 6301467
CONNECTOR SPARE
PART CODES:
CN1 code 6319162
CN2 code 6323824
CN3 code 6319164
CN4 code 6316203
CN5 code 6316200
CN6 code 6316202
CN7 code 6316204
CN9 code 6316201
CN10 code 6319165
CN12 code 6299991
CN13 code 6325683
CN14 code 6319163

Bekijk gratis de handleiding van Sime Murelle 70 Box ErP, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkSime
ModelMurelle 70 Box ErP
CategorieNiet gecategoriseerd
TaalNederlands
Grootte8576 MB