Schneider TeSys LT LT4706 handleiding

4 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 1 van 4
W9 1636671 01 A03
02 - 2011
1/4
www.schneider-electric.com
A
LT47
pp
0.5 - 6 A
Type
LT 4706
LT 4730
LT 4760
Relay setting range
3 - 30 A
5 - 60 A
Operating and Function
b LT47, solid state overload relay, compares motor
current with preset load current threshold (LOAD).
b Motor currents are monitored through two internal
current transformers.
b CT hole size is 12 mm in diameter. Please don't
allow excessive force on CTs.
b D-Time counts down and is only available for motor starting.
During steady state, if motor current is greater than current
setting(overloaded), LT47 switches its contacts after O-Time.
b For shear-pin (mechanical shock) protection, set O-Time knob
to its minimum in order to trip in 0.2-0.3 s.
DANGER
HAZARD OF ELECTRIC SHOCK,
EXPLOSION, OR ARC FLASH
Disconnect all power before servicing
equipment.
Failure to follow these instructions
will result in death or serious injury.
PLEASE NOTE:
b Electrical equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
b No responsibility is assumed by Schneider Electric
for any consequences arising out of the use of this
material.
b This document is also available in French, Spanish,
Italian, German, and Chinese for download on our
website at www.schneider-electric.com.

Bekijk gratis de handleiding van Schneider TeSys LT LT4706, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkSchneider
ModelTeSys LT LT4706
CategorieNiet gecategoriseerd
TaalNederlands
Grootte420 MB

Caratteristiche Prodotto

Gewicht192 g
Breedte71 mm
Diepte77.2 mm
Hoogte70.3 mm
Gewicht verpakking201 g