PowerLogic
TM
HDPM6000 Installation Guide
Safety Precautions
iii
!
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Submetering equipment shall not be mounted within 50.8 mm (2 in.) of
any live parts including primary conductors, primary terminals, primary
lugs. This requirement excludes insulated cables.
• Submeters attached to the enclosure shall not contact the panel interior
insulation.
• Mounting provisions shall not be attached to any live part.
• Voltage sensing and power supply connections to the primary voltage
shall have overcurrent protection.
• Do not install submetering equipment in any area where breaker arc
venting exhaust gasses could be re-directed as a result of submetering
equipment installation.
• This product must be installed inside a suitable re and electrical
enclosure.
• Follow safe electrical work practices. See NFPA 70E in the USA, or
applicable local codes.
• This equipment must only be installed and serviced by qualied electrical
personnel.
• Do not use this device for critical control or protection applications where
human or equipment safety relies on the operation of the control circuit.
• Do not install this product in hazardous or classied locations.
• Read, understand and follow the instructions before installing this
product.
• Turn o all power supplying equipment before working on or inside the
equipment.
• Product may use multiple voltage/power sources. Disconnect all sources
before servicing.
• Use a properly rated voltage sensing device to conrm that power is o.
• Do not use data from this device to conrm power is o.
• Replace all doors, covers and protective devices before powering the
equipment.
• Do not exceed the product's ratings or maximum limits.
• Treat communications and I/O wiring connected to multiple devices as
hazardous live until determined otherwise.
Failure to follow these instructions will result in death or serious
injury.
If this product is used in a manner not specied by the manufacturer, the
protection provided by the product may be impaired.
The installer is responsible for conformance to all applicable codes.
The safety of any system incorporating this equipment is the responsibility
of the assembler of the system.
Note: See IEC 60950-1:2005, Annex W for more information on
communications and I/O wiring connected to multiple devices.
Protective bonding: electrical connection of accessible conductive parts
or protective screening to provide electrical continuity to the means for
connection of an external protective conductor.
Bekijk gratis de handleiding van Schneider PowerLogic HDPM6000, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Schneider |
| Model | PowerLogic HDPM6000 |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 7028 MB |
Caratteristiche Prodotto
| Breedte | 221.74 mm |
| Diepte | 104.65 mm |
| Hoogte | 51.04 mm |
| Gewicht verpakking | 1800 g |
| Breedte verpakking | 356 mm |