Schneider Altivar 71 VW3A7201 handleiding
Handleiding
Je bekijkt pagina 33 van 38

1757361 06/2012 33
Starting tests
Initial power-up
• Step 1: Connect the line supply.
- The braking unit is ready to operate after approximately 1 s.
• Step 2: Check that the braking unit is ready to be used.
- If the green LED only is on, the braking unit is ready to be used.
- If all the other LEDs are also on, as well as the green LED, there is interference. Eliminate the interference before starting up
(See section: “Troubleshooting”, page 36
).
• Step 3: Check that the drive is ready to be started up.
- Proceed in accordance with the drive manual.
CAUTION
RISKS OF INTERFERENCE
• Check the wiring of the braking unit (short circuits and ground faults) before it is
turned on for the first time
• If the wiring is not correct, unexpected operation of the drive and/or the braking unit
is possible.
Failure to follow these precautions can result in equipment damage.