Operating Principle
Compensation for loss of head (from the version V1.2IE02)
An additional step [Pr adj coeff] (O14) is automatically substracted from the PID feedback each time an auxiliary pump is started. These
reference steps compensate for a loss of pressure (loss of head) in the pipework due to an increase in flow rate.
• Compensation for loss of head is active when the [Pr adj coeff] (O14) parameter is other than 0.
• The new PID feedback is generated using "the virtual analog input" [Network AI] (AIU1).
The [Network AI] (AIU1) parameter is controlled by the pump switching card. It is therefore not possible to use the "virtual
analog input" with the "Compensation for loss of head" function.
PID feedback
O14
O14
O14
Time
Run
Run
Run
Stop
Stop
Stop
Auxiliary pump 1
Auxiliary pump 2
Auxiliary pump 3
PID feedback
Compensated
PID feedback