8 1765274 08/2012
6. Quick start
Operation Refer to
A How to realize a factory setting of the drive
In the menu:
[1 DRIVE MENU]
[1.12 FACTORY SETTINGS]
Select [Config. Source]: Macro-conf,
Select [PARAMETER GROUP LIST]: All
Programming manual
[1.12 FACTORY SETTINGS]
(FCS-)
B How to configure main BACnet communication parameters:
In the menu:
[1 DRIVE MENU]
[1.9 COMMUNICATION]
[BACnet]
Check [Address] (BACnet MAC address)
Configure [Bit rate]
Configure [Instance number] (also called "Device node ID")
You must power cycle the drive to apply these parameters to the BACnet card.
7. Configuration
7. 1. Communication parameters
C How to configure control is from BACnet
In the menu:
[1 DRIVE MENU]
[1.6 COMMAND]
Change [Ref.1 channel] from "AI1" to "Com. card"
7. Configuration
7. 3. Control
D Handle the drive by the BACnet controller
Control the velocity setpoint by the analog value INPUT REF 1,
Control start / stop by the binary value RUN/STOP CMD,
Control direction of rotation by the binary value FWD/REV CMD,
Monitor if the drive is controlled local or remote (BACnet) by the binary value HAND/AUTO ACT,
Monitor the running / stopped state by the binary value RUN/STOP ACT,
Monitor the actual direction of rotation by the binary value FWD/REV ACT,
Monitor the actual speed or frequency by the analog value OUTPUT SPEED or ACTUAL FREQ.
Note: send first the reference (INPUT REF 1) before sending (RUN/STOP CMD) in order to start
the drive.
Fault handling:
Monitor the fault state by the binary value FAULT ACT,
Monitor the fault detail by the analog value LAST FLT,
Remote reset the fault by the binary value FAULT RESET.
E Switch local / remote by the drive HMI
Press F4 key (marked TK) to switch alternately from between BACnet and HMI.
The right of the upper display line:
- REM: control by BACnet,
- LOC: control by HMI.
Programming manual
Graphic display terminal
Description of the graphic screen
F Diagnose BACnet communication by the drive HMI
In the menu:
[1 DRIVE MENU]
[1.2 - MONITORING]
[COMMUNICATION MAP]
[DIAG NETWORK]
Monitor the frame and error frame counters.
8. Diagnostics
8. 3. Control - Command
G Diagnose BACnet communication by the drive HMI
In the menu:
[1 DRIVE MENU]
[1.2 - MONITORING]
[COMMUNICATION MAP]
Check that the Command Channel is Com. card,
Check that Active ref. channel is Com. card.
8. Diagnostics
8. 9. Communication
H Disable network fault for testing
In the menu:
[1 DRIVE MENU]
[1.8 FAULT MANAGEMENT] (FLt- )
Configure [COM. FAULT MANAGEMENT] to [Ignore].
Programming manual
[1.8 FAULT MANAGEMENT]
(FLt-)