Modbus 35
6180 F32 Section length value in meters
(used when section type is rec-
tangular)
From 0.001 to 3.
6190 F32 Section width value in meters
(used when section type is rec-
tangular)
From 0.001 to 3.
6200 F32 Airow coefcient (allows to cal-
culate an airow from the pres-
sure)
From 0.1 to 9999.9.
Probe Entry 2
6300 F32 Lower limit of probe range, for
each available measure
For maximum 10 measures (@6300:
lower range of measure1, @6302:
lower range of measure2, etc…).
6320 F32 Upper limit of probe range, for
each available measure
For maximum 10 measures (@6300:
upper range of measure 1, @6302:
upper range of measure 2, etc…).
6340 U8 Atmospheric pressure compen-
sation unit
cf. units enumeration
6350 F32 Atmospheric pressure compen-
sation value. In case of pressure,
this value is used for velocity cal-
culation
In Pa.
6360 U8 Type of pressure equipment
plugged in order to determine
the air velocity
0: Pitot tube S, 1: Pitot tube L, 2:
Debimo blades, 3: other (set pressu-
reEquipmentCoeff instead), 4: None
6370 F32 Custom coefcient for pressure
device plugged in order to deter-
mine the air velocity
From 0.0001 to 9.9999.
6380 U8 Room volume unit cf. units enumeration
6390 F32 Room volume value in cubic
meter used for computing air re-
newing rate (ACR)
In cubic meter.
6400 U8 Measurement integration From 0 to 9.
6410 U8 Temperature compensation
mode
0: Use internal sensor, 1: Manual – re-
fer to user value, 2: Use probe id 0 (or
user if not present), 3: Use probe id 1
(or user if not present), 4: Use probe
id 2 (or user if not present).
6420 U8 Manual temperature compensa-
tion unit
cf. units enumeration
6430 F32 Manual temperature compensa-
tion value in Celsius degrees
From -50 to 50, in Celsius degrees.
6440 F32 Correction factor used for air ve-
locity and airow probes
From 0.2 to 2] - Used for air velocity
and airow probes (default = 1).
6450 U8 Type of section used for air ve-
locity and airow probes
0: rectangular, 1: circular, 2: other (set
airow coefcient instead), 3: None
(not congured)
6460 U8 Unit for section diameter, section
length and section width
cf. units enumeration