36 Modbus
6470 F32 Section diameter value in meters
(used when section type is circu-
lar)
from 0.001 to 3
6480 F32 Section length value in meters
(used when section type is rec-
tangular)
from 0.001 to 3
6490 F32 Section width value in meters
(used when section type is rec-
tangular)
from 0.001 to 3
6500 F32 Airow coefcient (allows to cal-
culate an airow from the pres-
sure)
from 0.1 to 9999.9
Module
6600 F32 Lower limit of probe range, for
each available measure
for maximum 10 measures (@6600:
lower range of measure 1, @6602:
lower range of measure 2, etc…)
6620 F32 Upper limit of probe range, for
each available measure
for maximum 10 measures (@6600:
upper range of measure 1, @6602:
upper range of measure 2, etc…)
6640 U8 Atmospheric pressure compen-
sation unit
cf. units enumeration
6650 F32 Atmospheric pressure compen-
sation value. In case of pressure,
this value is used for velocity cal-
culation
in Pa
6660 U8 Type of pressure equipment
plugged in order to determine
the air velocity
0: Pitot tube S, 1: Pitot tube L, 2:
Debimo blades, 3: other (set pressu-
reEquipmentCoeff instead), 4: None
6670 F32 Custom coefcient for pressure
device plugged in order to deter-
mine the air velocity
from 0.0001 to 9.9999
6680 U8 Room volume unit cf. units enumeration
6690 F32 Room volume value in cubic
meter used for computing air re-
newing rate (ACR)
in cubic meter
6700 U8 Measurement integration from 0 to 9
6710 U8 Temperature compensation
mode
0: Use internal sensor, 1: Manual – re-
fer to user value, 2: Use probe id 0 (or
user if not present), 3: Use probe id 1
(or user if not present), 4: Use probe
id 2 (or user if not present)
6720 U8 Manual temperature compensa-
tion unit
cf. units enumeration
6730 F32 Manual temperature compensa-
tion value in Celsius degrees
From -50 to 50, in Celsius degrees.
6740 F32 Correction factor used for air ve-
locity and airow probes
From 0.2 to 2 - Used for air velocity
and airow probes (default = 1).
6750 U8 Type of section used for air ve-
locity and airow probes
0: rectangular, 1: circular, 2: other (set
airow coefcient instead), 3: None
(not congured).
6760 U8 Unit for section diameter, section
length and section width
cf. units enumeration