Installation Procedure
34
English
Installation Procedure
4way cassette
1 Push the supplied drain hose as far as possible
over the drain socket.
2 Tighten the metal clamp as shown in the picture.
3 Wrap the supplied large sealing pad over the
metal clamp and drain hose to insulate and fix it
with clamps.
4 Insulate the complete drain piping inside the
building (field supply).
If the drain hose cannot be sufficiently set on a
slope
, fit the hose with drain raising piping (field
supply).
5 Push the drain hose up to insulation when
connecting the drain hose to drain socket.
Large seailng pad
Drain socket
Metal clamp
Drain hose
Drain pipe
Be sure to bond the drain
hose and the main pipe.
PVC Tube Joint +
VP25 (OD: 32 mm, ID: 25 mm)
Drain pipe
Dr
ain hose
CAUTION
Check that the indoor unit is level with the ceiling by
using the leveller.
• Install air ventilation to drain condensation
smoothly.
Air ventilation
Ceiling
• If it is necessary to increase the height of the
drain pipe, install the drain pipe straight within
300 mm from the drain hose port. If it is raised
higher than 550 mm, there may be water leaks.
Drain hose
Ceiling
20 mm or more
1/100 or more
Band joint
300 mm or less
300 to
550 mm
• Do not give the hose an upward gradient beyond
the connection port. This will cause water to flow
backwards when the unit is stopped, resulting in
water leaks.
Under gradient
Ceiling
DB68-13032A-00_IBIM_DVM R32 WindFree 1,4way_EU_EN_.indd 34DB68-13032A-00_IBIM_DVM R32 WindFree 1,4way_EU_EN_.indd 34 2024-07-29 오전 10:10:502024-07-29 오전 10:10:50