Installation Procedure
Step 2 Performing the gas leak test
To identify potential gas leaks on the indoor unit,
inspect the connection area of each refrigerant pipe
using a leak detector for R-410A.
Before recreating the vacuum and recirculating the
refrigerant gas, pressurize the whole system with
nitrogen (using a cylinder with a pressure reducer)
at a pressure above 4.1 MPa in order to immediately
detect leaks on the refrigerant fittings.
Made vacuum for 15 minutes and pressurizing
system with nitrogen.
1way cassette
Insulator
Liquid side
Gas side
4way cassette
Insulator
Liquid side
Gas side
Step 3 Insulating the refrigerant
pipes
Once you have checked that there are no leaks in the
system, you can insulate the piping and hose.
1 To avoid condensation problems, place
Acrylonitrile Butadien Rubber separately around
each refrigerant pipe.
No gap
NBR
NOTE
• Always make the seam of pipes face upwards.
CAUTION
• The insulation has to be produced in full
compliance wirh European regulation EEC /
EU 2037 / 2000 requiring the use of sheaths
insulation without using CFC and HCFC gases for
health and the environment.
2 Wind insulating tape around the pipes and drain
hose avoiding compressing the insulation too
much.
Indoor unit
Insulation cover pipe
Be sure to overlap the insulation.
Insulation pipe
CAUTION
• Be sure to wrap insulation tightly without any
gaps.