R-32 system arrangement requirements
The DVM S ECO R32 model uses slightly ammable R-32 refrigerant. To comply with enhanced tightness
refrigerating systems requirements of IEC 60335-2-40, this system is equipped with an outdoor-unit shut-off
valve and a remote-control alarm. If the instructions in this user manual are followed, no additional safety
devices are required. Follow the installation requirements below, to ensure the entire system is compliant
with relevant regulations.
Installing the outdoor unit
Make sure to install the outdoor unit outdoors. If the outdoor unit is installed indoors, additional measures
may be required to comply with relevant regulations. A terminal for external output is available in the outdoor
unit. This terminal can be used when additional measures should be taken. An external output signal occurs
if the R-32 sensor in the indoor unit detects a refrigerant leak, or the sensor has a malfunction or short circuit.
Based on this signal, safety measures required for the outdoor unit, such as ventilation system activation and
alarm activation, can be taken.
Installing the indoor unit
For details on indoor unit installation, refer to the installation and user manual that came with the indoor unit.
Outdoor units for the DVM S ECO R32 model are compatible with R-32-sensor-embedded indoor units only.
See the table below for minimum indoor installation areas depending on the amount of refrigerant charging
for the outdoor unit. The minimum installation area must be satised.
The indoor unit provides an additional output signal for external devices. This output signal occurs if the R-32
sensor in the indoor unit detects a refrigerant leak, or the R-32 sensor has a malfunction or short circuit. Based
on this signal, an additional ventilation system or alarm can be activated. For details on this option, refer to
the indoor unit installation manual.
m(kg)
Minimum required room area (A, m²)
No underground oor Underground Floor
Ceiling- mounted type Wall-mounted type Ceiling- mounted type Wall-mounted type
≤ 1.842 No requirement No requirement
2.2 4.3 5.3 6.5 8.0
2.4 4.7 5.8 7.1 8.7
2.6 5.1 6.3 7.7 9.4
2.8 5.5 6.8 8.3 10.1
3 5.9 7.2 8.9 10.9
3.2 6.3 7.7 9.5 11.6
3.4 6.7 8.2 10.1 12.3
3.6 7.1 8.7 10.7 13.0
3.8 7. 5 9.2 11.3 13.8
4 7.9 9.7 11.8 14.5
4.2 8.3 10.1 12.4 15.2
4.4 8.7 10.6 13.0 15.9
4.6 9.1 11.1 13.6 16.6
4.8 9.5 11.6 14.2 1 7.4
5 9.9 12.1 14.8 18.1