ENGLISH-8
m(kg)
Minimum required room area (A, m²)
No underground oor Underground Floor
Ceiling- mounted type Wall-mounted type Ceiling- mounted type Wall-mounted type
5.2 10.3 12.5 15.4 18.8
5.4 10.7 13.0 16.0 19.5
5.6 11.1 13.5 16.6 20.3
5.8 11.5 14.0 17. 2 21.0
6 11.8 14.5 17.8 21.7
6.2 12.2 15.0 18.4 22.4
6.4 12.6 15.4 19.0 23.2
6.6 13.0 15.9 19.5 23.9
6.8 13.4 16.4 20.1 24.6
7 13.8 16.9 20.7 25.3
7. 2 14.2 17.4 21.3 26.1
7.4 14.6 17.9 21.9 26.8
7.6 15.0 18.3 22.5 2 7. 5
7.8 15.4 18.8 23.1 28.2
8 15.8 19.3 23.7 29.0
8.2 16.2 19.8 24.3 29.7
8.4 16.6 20.3 24.9 30.4
8.6 1 7.0 20.8 25.5 31.1
8.8 1 7.4 21.2 26.1 31.8
9 17.8 21.7 26.7 32.6
9.2 18.2 22.2 2 7. 2 33.3
9.4 18.6 22.7 27.8 34.0
9.6 19.0 23.2 28.4 34.7
9.8 19.3 23.6 29.0 35.5
10 19.7 24.1 29.6 36.2
10.2 20.1 24.6 30.2 36.9
- m : Total refrigerant charge in the system
- A : Minimum required room area
▶ IMPORTANT: it’s mandatory to consider either the table 1 or taking into consideration the local law
regarding the minimum living space of the premises.
▶ Minimum installation height of indoor unit is 1.8 m for wall, 2.2 m for ceiling.
R-32 system arrangement requirements