Installation Procedure
Installation Procedure
English
Indoor power supply
Power supply Max/Min(V) Indoor power cable
220-240V, 50 Hz
±10%
1.5 mm², 3 wires
Communication cable
0.75 mm², 2 wires
A
B
D
E
C
F
AC power: M4 screw
Communication: M3.5 screw
MODEL A B C D E F
AC012TNMPEC 9.8 12.6 19.0 7.5 9.0 13.8
AC018TNMPEC 9.8 12.6 19.0 7.5 9.0 13.8
AC024TNMPEC 9.8 12.6 19.0 7.5 9.0 13.8
AC030TNMPEC 9.8 12.6 19.0 7.5 9.0 13.8
AC036TNMPEC 9.8 12.6 19.0 7.5 9.0 13.8
AC042TNMPEC 9.8 12.6 19.0 7.5 9.0 13.8
AC054TNMPEC 10.3 13.8 19.2 8.4 9.5 19.2
AC060TNHPEC 10.3 13.8 19.2 10.1 11.4 19.2
Tightening torque (kgf • cm)
M3.5 8.0 to 12.0
M4 12.0 to 18.0
• 1 N·m = 10 kgf·cm
• Power supply cords of parts of appliances for
outdoor use shall not be lighter than polychloroprene
sheathed flexible cord. (Code designation IEC:60245
IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 /
CENELEC: H07RN-F)
• Since it has the external power supply, refer to the
outdoor unit installation manual for MAIN POWER.
CAUTION
• When installing the indoor unit in a computer
room or a server room, use the double shielded
communication cable (tape aluminum / polyester
braid + copper) of FROHH2R type.
Step 14 Optional: Extending the
power cable
1 Prepare a crimping tool and the following tools.
Tools Spec Shape
Crimping pliers MH-14
Connection sleeve
(mm)
20xØ6.5
(HxOD)
Insulation tape
Width 19
mm
Contraction tube
(mm)
70xØ8.0
(LxOD)
2 As shown in the figure, peel off the shields from the
rubber and wire of the power cable.
• Peel off 20 mm of the wire shields of the tube.
CAUTION
• For information about the power cable specifications for
indoor and outdoor units, refer to the installation manual.
• After peeling off the tube wire, you must insert a
contraction tube.
• If cable wires are connected without using connecting
sleeves, their contact area becomes reduced, or
corrosion develops on the outer surfaces of the wires
(copper wires) over a long time. This may cause an
increase of resistance(reduction of passing current)
and consequently may result in a fire.
Power cable
(Unit: mm)
20 20 20
60
120
180
202020
60
120
180
Pre-installed
tube for the
power cable
3 Insert both sides of core wire of the power cable into the
connection sleeve.
• Method 1: Push the core wire into the sleeve from
both sides.